[Apr 12, 2024] Prepare For The CDCP Question Papers In Advance
CDCP PDF Dumps Real 2024 Recently Updated Questions
NEW QUESTION # 29
Which type of Humidifier rapidly vibrates waster to create a fog or mist?
- A. Infrared Humidifier
- B. Water Canister Humidifier
- C. Ultrasonic Humidifier
- D. Steam Canister Humidifier
Answer: C
Explanation:
An ultrasonic humidifier is a type of cool mist humidifier that uses a metallic diaphragm that vibrates at high frequencies to create water droplets that are added to the air. A fan projects these droplets into the air as mist, which then evaporates and humidifies the room. This type of humidifier rapidly vibrates the water to create a fog or mist.
References: EPI Data Centre Training Framework, How Humidifiers Can Help Allergies, Humidifier Buying Guide: Pros and Cons of Different Types.
NEW QUESTION # 30
An optical fiber cable comes with the specifications 50/125 um.
What do the numbers represent?
- A. The first number represents the diameter of the core; the second number represents the actual diameter cable including the buffer and jacket.
- B. The first number represents the distance for a 10 Gb/s connection; the second number represents the distance for a 1 Gb/s connection.
- C. The first number represents the required distance to single-phase power cabling; the second number represents the required distance to three-phase cabling.
- D. The first number represents the diameter of the core; the second number represents the diameter of the cladding in microns.
Answer: D
Explanation:
Optical fiber cables are composed of a core, a cladding, and a coating. The core is the central part of the fiber that carries the light signal. The cladding is the layer surrounding the core that reflects the light back into the core and prevents signal loss. The coating is the protective layer that covers the cladding and provides mechanical strength and environmental protection. The specifications of an optical fiber cable indicate the dimensions of the core and the cladding in microns (m), which are one millionth of a meter. For example, a
50/125 m cable has a core diameter of 50 m and a cladding diameter of 125 m. The coating diameter is usually
250 m, but it is not part of the specifications.
References: Multimode Optical Fiber Selection & Specification - Corning, Optical Fiber OM3 (50/125µm Multimode Fiber), 50/125 Graded-Index OM2 Optical Fiber - OFS
NEW QUESTION # 31
What is a requirement of an FM200 (HFC-227) installation?
- A. Install pre-action sprinklers in the same room as the FM200.
- B. It is a high-pressure gas; therefore nozzles must be mounted with two brackets.
- C. Install the gas containers (tanks) close to the data centre.
- D. Drainage system under the raised floor.
Answer: B
Explanation:
FM200 (HFC-227) is a clean agent fire suppression system that uses a high-pressure gas to extinguish fires by reducing the oxygen concentration and absorbing the heat. FM200 is stored in cylinders at pressures of up to
42 bar (600 psi) and is released through nozzles into the protected area. Because of the high pressure, the nozzles must be mounted with two brackets to prevent them from moving or breaking during discharge. The brackets must be securely attached to the ceiling or wall and aligned with the nozzle outlet. The nozzle outlet must also be free of any obstructions that could affect the discharge pattern or distribution.
References:
*EPI Data Centre Professional (CDCP®) Preparation Guide, page 32
*FSL-227 Technical Manual, page 10
*Firetrace ILP Manual, page 21
NEW QUESTION # 32
Which one of the following is a core objective of a Business Value in an organization?
- A. None of the above
- B. Reducing Costs
- C. Reducing the Deficit
- D. Increasing Sales
Answer: A
Explanation:
According to the EPI Data Centre Professional (CDCP®) Reference Materials, a core objective of a Business Value in an organization is to create value for customers and stakeholders1. This means delivering products or services that meet or exceed customer expectations, while also generating profits or benefits for the organization and its shareholders. Reducing costs, reducing the deficit, and increasing sales are possible ways to achieve this objective, but they are not the core objective itself.
References: 1: EPI Data Centre Professional (CDCP®) Reference Materials, page 9.
NEW QUESTION # 33
IP protection grades consist of two numbers.
Which levels of protection do they describe and what is the best protection?
- A. First digit; protections against the ingress of water/fluids. Second digit; protection against ingress of solid objects. The lower the number the better the level of protection.
- B. First digit; protections against the ingress of solid objects. Second digit; protection against ingress of water/fluids. The higher the number the better the level of protection.
- C. First digit; protections against the ingress of solid objects. Second digit; protection against ingress of water/fluids. The lower the number the better the level of protection.
- D. First digit; protections against the ingress of water/fluids. Second digit; protection against ingress of solid objects. The higher the number the better the level of protection.
Answer: B
Explanation:
IP protection grades are a way of showing the effectiveness of electrical enclosures in blocking foreign bodies such as dust, moisture, liquids, and accidental contact. IP stands for Ingress Protection or International Protection, and it is defined by the international standard IEC 60529. IP ratings consist of the letters IP followed by two digits and an optional letter. The first digit indicates the level of protection the enclosure provides against access to hazardous parts and the ingress of solid foreign objects. The second digit indicates the level of protection the enclosure provides against the ingress of water or fluids. The higher the number, the better the level of protection. For example, IP65 means the enclosure is dust-tight and can withstand water jets from any direction. IP68 means the enclosure is dust-tight and can be submerged in water under specified conditions.
References: EPI Data Centre Training Framework, CDCP Preparation Guide, IP code - Wikipedia, [IP Ratings Explained | Ingress Protection Rating | IP Codes | Updated 2022]
NEW QUESTION # 34
Which Class of Fires involves energized electrical equipment?
- A. Class A
- B. Class B
- C. Class C
- D. Class K
Answer: C
Explanation:
Class C fires involve energized electrical equipment, such as computers, servers, switches, cables, and wiring.
These fires require the use of non-conductive extinguishing agents, such as carbon dioxide, dry chemical, or clean agent, to prevent electrical shock and damage to the equipment. Water-based extinguishers, such as Class A or K, are not suitable for Class C fires, as water can conduct electricity and cause electrocution or short circuits.
References: EPI Data Centre Training Framework, CDCP Preparation Guide, ABCs of Fire Extinguishers
NEW QUESTION # 35
Which one of the following is used in Measuring Business Value?
- A. Regeneration Cost
- B. Upfront Cost
- C. Scalability
- D. Reliability
Answer: C
Explanation:
Measuring business value is the process of assessing the benefits and costs of IT investments and initiatives in relation to the strategic objectives and priorities of the organization. One of the factors that can be used to measure business value is scalability, which is the ability of a system or component to handle increasing workloads or demands without compromising performance, quality, or functionality. Scalability is important for business value because it enables the organization to adapt to changing market conditions, customer expectations, and growth opportunities. Scalability can also reduce operational costs, increase efficiency, and improve customer satisfaction. Therefore, scalability is one of the factors that can be used in measuring business value.
References:
*EPI Data Centre Training Framework1
*EPI Data Centre Competence Framework2
*Measuring the Business Value of IT3
*How to Measure the Business Value with Effective Data Quality Governance
*7 Rules for Demonstrating the Business Value of IT
NEW QUESTION # 36
is the arithmetic mean of time between the failing and the subsequent running of the system in a particular time period.
- A. MCBF
- B. MTTR
- C. MLBF
- D. MTBF
Answer: D
Explanation:
MTBF stands for Mean Time Between Failures, and it is the arithmetic mean of time between the failing and the subsequent running of the system in a particular time period. MTBF is a measure of reliability that indicates how often a system or component fails during its operation. MTBF can be calculated by dividing the total operating time by the number of failures over a given period. For example, if a system operates for 1000 hours and experiences 5 failures, the MTBF is 1000/5 = 200 hours.
References: EPI Data Centre Training Framework, CDCP Preparation Guide, MTBF, MTTR, MTTF, MTTA:
Understanding incident metrics - Atlassian
NEW QUESTION # 37
Which Class of Fire involves combustible metals or combustible metal alloys such as magnesium, sodium and potassium?
- A. Class A
- B. Class D
- C. Class B
- D. Class C
Answer: B
Explanation:
Class D fires involve combustible metals or combustible metal alloys such as magnesium, sodium and potassium. These metals can react violently with water, air, or other chemicals, and require special extinguishing agents1 References: 1: EPI Data Centre Professional (CDCP®) Reference Materials, page 16.
NEW QUESTION # 38
Which one of the following does a Physical Infrastructure consists of in a Data Centre?
- A. Hub
- B. Server
- C. Rack
- D. Switch
Answer: C
Explanation:
A physical infrastructure in a Data Center consists of racks, which are metal frames used to store and organize server and other IT equipment. The racks are usually arranged in rows and columns, and they can be used to hold servers, storage devices, and other pieces of IT equipment. The racks can also be used to organize cables and other components to ensure that the Data Center is kept organized and efficient.
NEW QUESTION # 39
Which is the most damaging type of floor load?
- A. All loads are equally damaging to raised floor tiles
- B. Rolling Load (RL)
- C. Uniformly Distributed Load (UDL)
- D. Concentrated Load / Point Load (CP/ PL)
Answer: B
Explanation:
The most damaging type of floor load for raised floor tiles in a data centre is the rolling load (RL), according to the CDCP Preparation Guide1 and various web sources234. A rolling load is the load that is applied by a moving object, such as a pallet jack, a forklift, or a rack on wheels. A rolling load can cause more stress and fatigue on the raised floor tiles than a static load, such as a concentrated load (CP) or a uniformly distributed load (UDL), because it creates dynamic forces and impacts that can crack, dent, or deform the tiles. Moreover, a rolling load can also damage the pedestals and stringers that support the tiles, and cause the tiles to become loose or misaligned. Therefore, when designing and installing a raised floor system, it is important to consider the maximum rolling load that the tiles can withstand, and to use appropriate materials and methods to enhance the strength and durability of the tiles. For example, some possible solutions include using steel or concrete-filled tiles, reinforcing the edges and corners of the tiles, and using locking or gravity-held systems to secure the tiles.
References:
1: CDCP Preparation Guide, page 23, section 2.4.2 2: Top 5 Considerations - Selecting a Data Center Raised Floor Tile5, page 1, section 1 3: Raised Floor Systems: Explained, Improved and Reinvented6, page 1, section
1 4: Raised Floor Systems: Common Problems and Solutions7, page 1, section 1
NEW QUESTION # 40
Does unplanned downtime of a data centre have an impact on the business results?
- A. Yes, data centre downtime can result in business downtime.
- B. Yes, but data centre downtime only impacts the airline industry.
- C. No, unplanned data centre downtime is already financially planned for in the yearly budget planning process.
- D. No, because data centres operate independently from the business.
Answer: A
Explanation:
Data centres are essential for supporting the IT operations and applications of various businesses across different industries. Data centre downtime can have a negative impact on the business results, such as loss of revenue, customer satisfaction, productivity, reputation, and competitive advantage. According to a web search, the average cost of data centre downtime in 2020 was $8,851 per minute, and the average duration of a data centre outage was 95 minutes1. This means that a typical data centre outage could cost a business over
$840,000 in direct and indirect losses1. Therefore, data centre downtime can have a significant impact on the business results, regardless of the industry or sector.
References: Unplanned Downtime Costs More Than You Think, Downtime, Outages and Failures - Understanding Their True Costs, The Unplanned Downtime Nightmare - And How Operators Can Avoid
NEW QUESTION # 41
What is the purpose of a service corridor?
- A. It provides a safe, vented and secure area where standby generators can operate safely.
- B. To create a secure and conditioned environment where media can be stored in a controlled manner.
- C. It is a generic name for pathways leading to other rooms that contains facility supporting equipment like the UPS room, battery room, generator room etc.
- D. It provides a secure area where supporting facilities can be serviced and monitored on a 24x7 basis without disturbing the computer room.
Answer: D
Explanation:
A service corridor is a dedicated space within or adjacent to a data centre that allows access to the supporting facilities, such as power, cooling, fire suppression, security, and cabling systems, without interfering with the computer room operations. A service corridor helps to isolate the noise, vibration, heat, and dust generated by the supporting facilities from the sensitive equipment in the computer room. A service corridor also enhances the safety and efficiency of the maintenance and monitoring activities, as well as the flexibility and scalability of the data centre design.
References: EPI Data Centre Training Framework, CDCP Preparation Guide, Service Corridors Definition | Law Insider
NEW QUESTION # 42
Which one of the following is an AC Power Quality Anomaly?
- A. Attenuation
- B. Backup Condition
- C. Waveform Distortion
- D. Signal Distortion
Answer: C
Explanation:
Waveform distortion is a type of AC power quality anomaly that occurs when the shape of the voltage or current waveform deviates from the ideal sinusoidal shape. Waveform distortion can be caused by nonlinear loads, such as rectifiers, inverters, variable frequency drives, and electronic devices, that draw current in pulses or harmonics. Waveform distortion can result in overheating, reduced efficiency, malfunctioning, or damage of equipment.
References: EPI Data Centre Training Framework, CDCP Preparation Guide, 5 anomalies in AC power that can damage your home devices, 9 Most Common Power Quality Problems
NEW QUESTION # 43
Cost of Downtime can be classified as.
- A. Classified and Declassified
- B. Mean and Median
- C. Up and Down
- D. Direct and Indirect
Answer: D
Explanation:
Cost of downtime is the total amount of money lost due to a data centre outage or disruption. It can be classified into two categories: direct and indirect. Direct costs are the immediate and measurable expenses incurred during or after an outage, such as lost revenue, lost productivity, recovery costs, compensation costs, penalties, etc. Indirect costs are the long-term and intangible impacts of an outage, such as reputation damage, customer dissatisfaction, loss of market share, legal liabilities, etc. Both direct and indirect costs can vary depending on the type, duration, and severity of the outage, as well as the industry, size, and location of the data centre.
References:
*EPI Data Centre Training Framework1
*EPI Data Centre Competence Framework2
*Understanding the Cost of Data Center Downtime3
*Uptime Institute's 2022 Outage Analysis Finds Downtime Costs and Consequences Worsening
*[INFOGRAPHIC] The Cost of Downtime: 21 Stats You Need to Know
NEW QUESTION # 44
What is a requirement for both CCTV cameras and recording equipment?
- A. They must be of the same brand.
- B. CCTV cameras can only be used to cover the outside of the building, where as the recording equipment needs to be located in a secure area.
- C. Both must be connected to a UPS.
- D. Both must be placed inside the Computer room.
Answer: C
Explanation:
A UPS (Uninterruptible Power Supply) is a device that provides backup power to electrical equipment in case of a power outage or fluctuation. A UPS is essential for both CCTV cameras and recording equipment, as it ensures that the surveillance system can continue to operate and record without interruption or data loss. A UPS can also protect the CCTV cameras and recording equipment from damage caused by power surges or spikes. Connecting both CCTV cameras and recording equipment to a UPS is a requirement for data centres, as it enhances the security and reliability of the surveillance system.
References: Technical Specification - GeM, [What is a UPS? | Uninterruptible Power Supply | APC by Schneider Electric], [Why You Need a UPS for Your CCTV System - CCTV Camera World].
NEW QUESTION # 45
Which Class of Fires involves cooking appliances?
- A. Class A
- B. Class B
- C. Class C
- D. Class K
Answer: D
Explanation:
According to the EPI Data Centre Professional (CDCP®) Preparation Guide, Class K fires involve cooking appliances that use combustible cooking media such as vegetable or animal oils and fats (page 28). Class K fires require special extinguishing agents that can suppress the high-temperature flames and prevent re-ignition. Class K fires are different from Class B fires, which involve flammable liquids such as gasoline, oil, or paint.
References:
*EPI Data Centre Professional (CDCP®) Preparation Guide, page 28
*Fire Classes and Extinguishing Agents | The Fire Equipment Manufacturers' Association
NEW QUESTION # 46
Measuring "Business Values" begins first with.
- A. Budget
- B. Topology
- C. Physical Infrastructure
- D. Network
Answer: A
Explanation:
Measuring "Business Values" begins first with budgeting and identifying the costs associated with the project.
This includes understanding the economic impact of the project, such as the cost of labor, materials, and other resources. It is also important to evaluate the return on investment (ROI) of the project, which will help to determine its overall value. Additionally, it is important to consider the long-term impact of the project and its potential to add value to the business in the future.
NEW QUESTION # 47
Which of statements below is true?
- A. Multi-mode cabling can cross longer distances.
- B. Single-mode cabling is more expensive than multi-mode cabling.
- C. Multi-mode cabling is more expensive than single-mode cabling.
- D. Single-mode cabling can use both LED and laser as a light source.
Answer: B
Explanation:
Single-mode cabling and multi-mode cabling are two types of fiber optic cables that differ in their core diameter, wavelength, light source, bandwidth, distance, and cost. Single-mode cabling has a smaller core diameter and uses a laser as a light source, which enables it to transmit data over longer distances and higher bandwidths. However, single-mode cabling is also more expensive than multi-mode cabling, because it requires more precise alignmentand splicing, and more costly light sources and connectors. Multi-mode cabling has a larger core diameter and uses LEDs or VCSELs as a light source, which makes it cheaper and easier to install and maintain. However, multi-mode cabling also has a shorter distance and lower bandwidth than single-mode cabling, because it suffers from more modal dispersion and attenuation.
References:
1: Data Center Cabling: Single Mode vs Multimode Fibers2, page 1, section 1 3: Single Mode vs Multimode Fiber Cable Guide4, page 1, section 1 5: Single-Mode vs. Multi-Mode Fiber Cables: Explained6, page 1, section 1 7: 2 Types of Fiber Optic Cable: Single Mode vs. Multimode Fiber8, page 1, section 1
NEW QUESTION # 48
What is the recommended location for the Isolation Transformer in relation to the ICT-Equipment location?
- A. The isolation transformer should be as close as possible to the ICT equipment but taking into account potential EMF.
- B. The isolation transformer should be installed within the rack in which the ICT equipment has been installed.
- C. The isolation transformer should be as far away as possible to the ICT equipment to avoid potential EMF.
- D. The isolation transformer has to be installed within the power entry point of the building due to electrical code (regulation) requirements.
Answer: A
Explanation:
According to the EPI Data Centre Training Framework, an isolation transformer is a device that transfers electrical power from one circuit to another without changing the voltage or frequency, but providing galvanic isolation1. Galvanic isolation means that there is no direct electrical connection between the input and output circuits, which can prevent ground loops, reduce noise, and improve safety2. An isolation transformer can also provide voltage stepdown or stepup, create a local ground-bonded neutral, reduce harmonic currents, and provide taps for abnormal mains voltage3.
The location of the isolation transformer in relation to the ICT equipment depends on the purpose and design of the transformer. In general, the isolation transformer should be as close as possible to the ICT equipment, but taking into account potential EMF4. EMF is a form of electromagnetic interference (EMI) that can affect the performance and reliability of the ICT equipment5. The closer the isolation transformer is to the ICT equipment, the shorter the cable length and the lower the voltage drop and power loss4. However, the isolation transformer should also be far enough from the ICT equipment to avoid EMF, which can be reduced by using proper shielding, grounding, and spacing5.
The isolation transformer should not be installed as far away as possible to the ICT equipment, as option B suggests, because this would increase the cable length and the voltage drop and power loss4. The isolation transformer does not have to be installed within the power entry point of the building, as option C suggests, because this is not a requirement of the electrical code or regulation, and it may not be optimal for the data centre power system. The isolation transformer should not be installed within the rack in which the ICT equipment has been installed, as option D suggests, because this would increase the heat load and the noise level in the rack, and it may not fit in the rack space.
References: 1: EPI Data Centre Training Framework, Module 5: Power, Section 5.4.3: Isolation Transformers, Page 5-38 2: Guidelines for using isolation transformers in data center UPS systems - EEP1, Page 1 3: The Role of Isolation Transformers in Data Center UPS Systems2, Page 2 4: Data Center Transformer | Power Distribution - FGC Construction3, Page 1 5: EPI Data Centre Training Framework, Module 5: Power, Section
5.4.1: Electromagnetic Interference, Page 5-34 : Data centre transformers manufacturers - TMC Transformers4, Page 1 : The Role of Isolation Transformers in Data Center UPS Systems2, Page 25
NEW QUESTION # 49
The temperature and humidity values indicated on the display of the Computer room air conditioner unit are the values measured at which point?
- A. It is the value measured at the intake of the air conditioner.
- B. It is the value measured at the exhaust (outlet) of the air conditioner.
- C. It is the value measured at the front of the rack of the aisle the air conditioner is situated.
- D. It is the average value between the intake and exhaust (outlet) of the air conditioner.
Answer: A
Explanation:
According to the IBM document on temperature and humidity design criteria1, the temperature and humidity values indicated on the display of the computer room air conditioner unit are the values measured at the intake of the air conditioner. This is because the intake is where the air conditioner draws the air from the computer room and cools and dehumidifies it before sending it back to the computer room. The display shows the current conditions of the computer room air, which are used to adjust the cooling and dehumidifying operations of the air conditioner. The values measured at the exhaust (outlet) of the air conditioner are not displayed, as they are not relevant for the computer room environment. The values measured at the front of the rack of the aisle the air conditioner is situated are also not displayed, as they may vary depending on the distance and location of the rack. The average value between the intake and exhaust (outlet) of the air conditioner is not displayed, as it does not reflect the actual conditions of the computer room air or the air conditioner performance.
References: 1: Temperature and humidity design criteria - IBM
NEW QUESTION # 50
What is the most preferred unit of measure for cooling capacity?
- A. Horsepower
- B. BTU
- C. Watt
- D. Ton
Answer: C
Explanation:
Cooling capacity is the measure of a cooling system's ability to remove heat from a space. The most preferred unit of measure for cooling capacity is watt (W), which is the SI unit for power. Watt is defined as the amount of energy transferred or converted per unit time. One watt is equal to one joule of energy per second. Using watt as the unit of measure for cooling capacity allows for easy comparison and calculation of the cooling performance and efficiency of different cooling systems.
Other units of measure for cooling capacity are ton, BTU, and horsepower, but they are less common and less convenient than watt. Ton is a unit of measure that describes how much water at freezing temperature can be frozen in 24 hours, equivalent to 3.5 kW or 12,000 BTU/h. BTU (British Thermal Unit) is a unit of measure that describes the amount of heat required to raise the temperature of one pound of water by one degree Fahrenheit, equivalent to 0.293 W. Horsepower is a unit of measure that describes the rate at which work is done, equivalent to 746 W.
References:
*Data Centre Professional (CDCP®) Reference Materials, page 8, section 2.1.1
*Data Centre Professional (CDCP®) Preparation Guide, page 11, section 2.1.1
*Cooling capacity - Wikipedia
*Air Conditioner BTU Calculator
*Air conditioning 101: Basics, working principle and sizing ... - GlobalSpec
*How is cooling capacity measured? - Sage-Advices
*Everything You Need to Know About Cooling Capacity
NEW QUESTION # 51
What is the minimum clearance space required below water sprinkler heads and nozzles of gas-based fire suppression systems?
- A. 64 cm / 25 inches
- B. 120 cm / 47 inches
- C. 60 cm / 24 inches
- D. 46 cm / 18 inches
Answer: D
Explanation:
The minimum clearance space required below water sprinkler heads and nozzles of gas-based fire suppression systems is 46 cm / 18 inches, according to the CDCP Preparation Guide1 and OSHA regulation 29 CFR
1910.159 © (10)2. This clearance space is necessary to ensure that the sprinkler spray or gas discharge can reach the fire and cover the protected area effectively. Any material or obstruction below this clearance space can interfere with the sprinkler or gas distribution and reduce the fire suppression performance. Therefore, building owners and managers should ensure that all storage and objects in the data centre are kept below this clearance space, and that the clearance space is maintained at all times.
References:
1: CDCP Preparation Guide, page 24, section 2.4.3 2: Clarification of OSHA regulation 29 CFR
1910.159©(10), Sprinkler ...3, page 1, section 1
NEW QUESTION # 52
Which type of Fire Detection Device is recommended for protecting a Data Center?
- A. None of the above
- B. Flame detector
- C. Heat detector
- D. Smoke detector
Answer: D
Explanation:
According to the CDCP® Preparation Guide, smoke detectors are the most common type of fire detection devices used in data centers, as they can detect a fire in its early stages and provide early warning to the occupants and authorities. Smoke detectors can be either spot-type or air-aspirating, depending on the design and goals of the data center. Spot-type detectors are inexpensive and simple, but may cause activation delay and false alarms. Air-aspirating detectors are more sensitive and reliable, but may require more maintenance and installation costs. Both types of detectors should be installed in accordance with the relevant standards and codes, such as NFPA 72 and EN 54.
References: CDCP® Preparation Guide, page 30-31. Evaluating Fire Detection Options For Data Centers. Fire Detection and Suppression Systems in a Data Center.
NEW QUESTION # 53
......